Chapter 4: Management with WebPAM PROe
117
Enclosure Settings
The Enclosure–Settings tab enables you to make settings for certain components
of the VTrak subsystem enclosure. To make Enclosure settings:
1. Click the Subsystem icon in Tree View.
2. Click on the Enclosures icon.
3. Click on the Enclosure icon.
4. Click on the Settings tab in Management View.
5. Enter a polling interval (15 to 255 seconds) in the Polling Interval field.
6. Enter a value in the Enclosure Warning Temperature Threshold field (45°C is
the default)
7. Enter a value in the Enclosure Critical Temperature Threshold field (51°C is
the default)
8. Enter a value in the Controller Warning Temperature Threshold field (63°C is
the default)
9. Enter a value in the Controller Critical Temperature Threshold field (68°C is
the default)
10. Click the Submit button.
The changes take effect immediately.
FRU VPD
The Enclosure–FRU VPD tab displays Vital Product Data (VPD) information
about Field Replaceable Units (FRU) in the VTrak subsystem enclosure,
including:
Controller Motherboard
Storage Enclosure Processor (SEP)
Battery Backup Unit (BBU)
Cooling Units
Power Supply Units
Back Plane
Controller Daughter Card Battery
Use this information when communicating with Technical Support and when
ordering replacement units. For contact information, see “Contact Technical
Support” on page 293.
To access Controller information:
1. Click the Subsystem icon in Tree View.
2. Click on the Enclosures icon.